| CONTENTS
|
Ski Trip
Dead in the
Water
Code
Calculations
What's
Wrong
Here?
Code Q&A
Code Quiz
Faces of the Code
Violation
Validation
EC&M Code Conference
|
|
About this Newsletter
|
This twice-a-month e-newsletter is brought to you from the
publisher of EC&M magazine. CodeWatch will:
Let you know what could be changing in the Code®.
Help you brush up on your ability to apply the Code®.
Test your knowledge of the Code® with a Q&A format.
Introduce you to the people who vote on the rule changes.
Provide information on upcoming Code® seminars and shows.
Give you an opportunity to sound off on Code®-related issues.
We want to make sure we're providing you with the content you need to
better manage your business or enhance your technical skills. E-mail us and
let us know what you want to see in future issues of this e-newsletter.
We will do our best to address your request in a future issue of
CodeWatch.
|
Subscriptions
|
|
To sign up
for your free subscription, click here: Subscribe
To unsubscribe from this newsletter click here: Unsubscribe
To get this newsletter in a different format (Text, AOL or HTML),
or to change your e-mail address, please visit your profile page to change your delivery
preferences.
|
Back Issues
|
|
Missed an
issue? Visit the
CodeWatch archive on EC&M's Web site.
|
Tell a friend about CodeWatch
|
|
Do you know
of someone who'd like to receive CodeWatch? Visit the subscriber site, enter their e-mail
address and spread the wealth!
|
Advertising
|
To find out
how to advertise in this newsletter, e-mail Bob MacArthur or call
him at (913) 967-1837.
The designations "National Electrical Code" and "NEC" refer to the
National Electrical Code®, which is a registered trademark of the
National Fire Protection Association.
|
| | | | |
|
Nightmare Installations
Ski Trip
While I was working on a bathroom remodeling project at
an old ski lodge, the plumber told me he would get shocked
when
he stuck his hand in the wet concrete that he was re-pouring in a
chase.
When my coworkers and I entered the bathroom we noticed a new copper
line directly over the hole he was filling. Upon testing the pipe we
read nothing to ground. When we pulled out our voltage indicators they
would glow anywhere in the room. We dragged an extension cord in from
another room but read nothing from the pipe to neutral or ground. After
tearing into several boxes inside the room we found a spread lock m/c
connector that had been overtightened and had no bushing pressed into
the m/c. The neutral was pierced by the cut edge of the metal covering
and had energized the whole ground system. The wet concrete created
potential between the energized pipe system and ground. The 60V was
just
enough to make our voltage indicators glow. The plumber was resting his
hand on the copper pipe and got shocked when he placed his hand in the
wet concrete. This was a perfect example of a poorly or unbonded water
system.
Mike Stauffer
Orem, Utah
ADVERTISEMENT
Accuracy and Diagnostic Functions for Maximum
Industrial Productivity
The new Fluke 87V has improved measurement functions,
trouble-shooting features, resolution and accuracy to solve more
problems on motor drives, in plant automation, power distribution and
electro-mechanical equipment.
Unique function for accurate voltage and frequency measurements
on
adjustable speed motor drives and other electrically noisy equipment
(87V)
Built-in thermometer conveniently allows you to take temperature
readings without having to carry a separate instrument (87V)
Visit our Web
site for more details.
Dead in the Water
Late one rainy Friday afternoon I was called by an
owner
to look at a recently approved permanent installation that had water
flowing through the meter socket into the base of the breaker panel.
When I arrived on-site the power company's transformer was about 4
inches deep in water. I proceeded to look at the meter socket and panel
that were both wet on the bottom of the boxes. Water was also flowing
out of a cracked conduit coupling. After calling the power company, I
found that the conduit installed to the house was underwater in the
transformer box and slightly above the elevation of both the meter
socket and the breaker panel. Having identified the source of the
problem, the power company extended the conduit to above the water line
and scheduled the raising of the transformer for the following week.
The
owner never wanted a water-cooled breaker electrical panel and neither
did the inspector.
Tim Crabb
Dubuque, Iowa
Send your 200-word story to us and it may
appear in a future issue of CodeWatch. Authors of stories chosen for
publication will receive $25.
ADVERTISEMENT
Ultraweld®
No Penalties for Expedited Shipments
You need it fast and don't want to pay those extra charges for
expedited
shipments? Then you need to check out Ultraweld®. We don't penalize
our customers for needing product in a hurry. No more paying for those
Fly Away or Fast Track charges with Ultraweld®. Get the Best from
the Best and don't pay extra to get it. Exothermic Cross Reference
available. Call us for details at (800) 842-7473.
www.harger.com
Applications Corner
Code Calculations
By Mike Holt
The requirements for protecting the branch-circuit
conductors, control apparatus, and circuits that supply hermetic
refrigerant motor-compressors against short circuits and ground faults
are noted in 440.22. The size and type of short-circuit and
ground-fault
protection device for air conditioning and refrigeration equipment are
often marked on the equipment nameplate. The manufacturer calculates
these ratings per 440.22 and 440.32. If the equipment nameplate
specifies "Maximum Fuse Size," use a one-time or dual-element fuse. If
the nameplate specifies "HACR Circuit Breaker," use a HACR-rated
circuit
breaker [110.3(B)].
Short-circuit and ground-fault protection can't exceed the nameplate
ratings. If the equipment doesn't have a nameplate that specifies the
size and type of protection device, how do you size those devices? That
depends on whether you're sizing for multiple motors or a single motor.
Visit EC&M's
Web site to see the answer.
ADVERTISEMENT
UL Listed ETP Raintight Fittings Have Inspection Aid
ETP UL Listed Raintight EMT steel couplings and connectors feature
exclusive InspectoRidge External Inspection Aid for faster
identification by inspectors. Formed on the outside of the coupling or
connector, it allows an inspector to visually determine that the
fitting
is raintight. Offered in 1/2-inch to 1-inch trade sizes, the fittings
have an internal sealing ring and gasket, along with a KO sealing ring.
Choose from insulated or non-insulated throat. The rugged steel
construction has a zinc electroplate finish. The fittings install with
standard electrician tools and methods. For information, call
800-621-1506. E-mail: literature@egseg.com
Code Challenge
What's Wrong Here?
By Joe Tedesco
How does this
installation violate NEC requirements?
Hint: Missing connections and so much more.
Code Q&A
By Mike Holt
Q. Can a single transfer switch be used to
supply
both emergency and non-emergency loads, such as a UPS for telecom
equipment?
See the answer.
Code Quiz
By Steve Owen
Consider a large industrial complex with multiple
buildings. According to the 2002 NEC, what would the proper location
for
the plaque or directory be for the eight 3,000A feeders that are
installed between the eight 2,500kVA substation, 480V secondaries
located outdoors and the eight 3,000A, 480V switchgear(s) located in
the
electrical room(s) inside one of the industrial buildings. This complex
is under single management.
- A sign shall be placed at each feeder location denoting
all other services, feeders, or branch circuits that supply that
building or structure or pass through that building or structure and
the
area served by each.
- A red sign shall be placed at each feeder location to denote all
other services, feeders, or branch circuits that supply or pass through
that building or structure and the area served by each.
- A plaque or directory shall not be required for large-capacity,
multibuilding industrial installations under single management, where
it's ensured that disconnection can be accomplished by establishing and
maintaining safe switching procedures.
- Each disconnecting means shall be marked as a "service
disconnect."
Visit EC&M's Web
site for the answer and explanation.
ADVERTISEMENT
Cool Electronic Cabinets
Low cost Cabinet Coolers prevent hot weather failures by keeping
electrical enclosures cool. UL Listed Cabinet Coolers produce 20 degree
Fahrenheit air from an ordinary supply of compressed air to cool
electrical controls. Thermostat control minimizes air usage. Maintains
the NEMA 4, 4X (stainless steel) and 12 rating of the enclosure. Web
site offers detailed information, downloadable drawings and PDF
literature.
www.exair.com
Faces of the Code
Ken
Vannice Member, Code-Making Panel 15
Plenty of electrical engineers who serve on NEC
code-making panels have two college degrees, but Ken Vannice is
probably
the only one who can say his second is in theater arts. Although vastly
different, the two have intersected in the least likely of places and
taken him from his work as a stage manager at his high school theater
in
Bozeman, Mont., to an engineering career in Portland, Ore., and a spot
on CMP-15 as a representative of the U.S. Institute for Theatre
Technology (USITT).
Not only is Vannice the principal, he was the entertainment
industry's first member to win a seat at the NEC table in 1988 -- he
still has the certificate of appointment hanging on his office wall.
Since then, along with representatives from the Motion Picture
Association of America and the International Alliance of Theatrical
Stage Employees, among others, Vannice has done his part to modernize
the special occupancy sections that apply to the theater. "We weren't
on
many people's radar, so we weren't bothered by the electrical
inspectors
very much," Vannice says. "But as we got more and more visible, we had
to deal with a Code that didn't relate to our equipment or our industry
anymore."
Electrical inspectors' lack of familiarity with the entertainment
industry in the mid-'80s was what led Vannice -- with the support of
the
USITT -- to join CMP-15. And the first order of business was to
demonstrate that even though they hadn't been closely monitored, they
were still safe. "There are a lot of things our industry has pioneered
because we needed it -- long before the NEC required it," he says.
"But
because we go about it in an unconventional way sometimes, inspectors
not familiar with what we do might question it. Once they understand
how
we do it, though, they can see it's safe."
Now a project manager for dimming products in Leviton's R&D
department in Portland, Vannice has given up his work behind the stage,
but he
still
has plenty of time to sit in front of it in the audience. The only
problem, though, is catching the shows while they're in town. "A show
that goes to L.A. will stay for a month or two, but it will only come
here for a week," he says. "You have to be aware of them and be on your
toes."
ADVERTISEMENT
www.NECcode.com
The National Electrical Code Internet Connection, the No. 1
rated Code Web site in the world, offers the following FREE products:
Books, Code Quiz, DVDs, Graphics for PowerPoint, Newsletter, Online
Training, Posters, Simulated Exams, Software, Video clips, and Videos
Visit www.NECcode.com and stay
current with important industry issues.
Speak Out
Violation
Validation
The entertainment industry outgrew the requirements of
the Code long before Ken Vannice joined CMP-15, so he and his fellow
entertainment engineers had to improvise, knowing that in some
instances
they were violating the NEC. When is it acceptable to violate the Code?
Visit EC&M's Web site to
tell
us.
Either 33% of CodeWatch readers are going to die soon or it may be a
while before fuel cells gain even a modest hold on the U.S. industrial
sector. One third of you believe you won't live to see 5% of industrial
facilities equip themselves with a fuel cell. In related news, the U.S.
fuel cell industry has begun research into the development of a
fountain
of youth.
Shows and Events
EC&M Code
Conference
Haven't signed up yet for one of EC&M's 2005
Code
Change Conferences? There's still time. Download
the registration form, and pick the closest seminar. Fill it out and
fax
it to (203) 929-5351. Registration for the first conference, to be held
in Atlanta on Oct. 27-28, is open through Aug. 27. And it's not too
late to take advantage of early bird registration for the San Francisco
and Seattle seminars, but procrastinators beware: the deadline for both
is Aug. 6. Moderated by Mike Holt and Fred Hartwell (Boston
conference
only), the two-day conferences will cover everything you need to know
about the 2005 Code. All attendees will receive a copy of the 2005 NEC
and EC&M's 2005 Code Change Book, written by Mike Holt.
|
|
You are subscribed to this newsletter as <*email*>
For questions concerning delivery of this
newsletter, please contact our Customer Service Department at:
US Toll Free: (866) 505-7173
International: (402) 505-7173
or custserv@newsletter.primediabusiness.com
Primedia Business Magazines & Media
9800 Metcalf Avenue
Overland Park, KS 66212
Copyright 2004, PRIMEDIA. All rights reserved. This article is
protected
by United States copyright and other intellectual property laws and may
not be reproduced, rewritten, distributed, re-disseminated,
transmitted,
displayed, published or broadcast, directly or indirectly, in any
medium
without the prior written permission of Primedia Business Magazines &
Media Inc.
|
|